2-Way Consumer Unit 100A Main Switch | UKCA Certified
£21.82
2 usable ways | 100A main switch | Plastic enclosure | UKCA Certified
2-Way Consumer Unit 100A Main Switch | UKCA Certified
The E0402 is a 2-way consumer unit fitted with a 100A double-pole main switch isolator, providing a reliable local isolation point for domestic and small commercial electrical installations. This consumer unit is designed for split-load configurations where the installer specifies the outgoing protection devices — allowing complete flexibility to populate the board with MCBs, RCBOs or a combination of RCDs and MCBs to suit the specific installation requirements.
With 2 usable ways and a robust 100A main switch, this unit is suitable for small domestic installations, flats and extensions. The metal enclosure is manufactured from powder-coated galvanised steel, meeting BS 7671 (18th Edition) Regulation 421.1.201 for consumer units in domestic premises. Cable entry is provided via top and bottom knockouts for flexible installation options.
Key Features
- 2 usable ways — compact board for small installations
- 100A double-pole main switch — provides safe local isolation of the entire installation
- Metal construction — powder-coated galvanised steel enclosure for fire resistance
- 35mm DIN rail — compatible with all MCBs, RCBOs and modular devices
- Neutral bar and earth bar included as standard
- Top and bottom cable entry knockouts — flexible installation options
- UKCA certified — compliant with UK product safety regulations
- Suitable for new installations, upgrades and consumer unit replacements
Technical Specification
| Product model | E0402 |
| Number of usable ways | 2 |
| Incomer type | 100A double-pole main switch isolator |
| Rated voltage | 240V AC (230V) |
| Construction | Powder-coated galvanised steel |
| DIN rail | 35mm (fitted) |
| Neutral bar | Included |
| Earth bar | Included |
| Cable entry | Top and bottom knockouts |
| Door type | Hinged metal door with catch |
| IP rating | IP30 (with door closed) |
| SKU | E0402 |
Compliance & Certification
- UKCA certified
- Metal enclosure as required by BS 7671 (18th Edition) Regulation 421.1.201
- 100A main switch provides isolation point as required by BS 7671 Regulation 537.1
- Suitable for use in installations compliant with BS 7671 (18th Edition IET Wiring Regulations)
Installation Notes
This consumer unit must be installed by a qualified electrician in accordance with BS 7671 (18th Edition IET Wiring Regulations). Always isolate the supply before installation. The 100A main switch provides a local means of isolation for the entire installation. The installer must specify and fit appropriate outgoing protection devices (MCBs, RCBOs or RCD + MCB combinations) to suit the circuits being supplied. Earth leakage protection must be provided on all circuits as required by BS 7671 — this can be achieved using RCBOs on each circuit, or by fitting RCDs in a split-load configuration. Mount the consumer unit on a flat, non-combustible surface at a height between 450mm and 1350mm from finished floor level (Part M accessibility requirements). Ensure all unused ways are fitted with blanking modules to maintain the enclosure IP rating.
Related products
10kA MCB – High Breaking Capacity Miniature Circuit Breaker
In stock
6-Way Consumer Unit 100A Main Switch + SPD | UKCA Certified
In stock
RCBO 30mA Type A — 1P+N Residual Current Circuit Breaker | UKCA Certified
In stock
RCBO 30mA Type AC — 1P+N Residual Current Circuit Breaker | UKCA Certified
In stock

Reviews
Clear filtersThere are no reviews yet.