Type 2 SPD 20kA 1P+N – Surge Protection Device for Consumer Units | UKCA Certified

£8.39

Type 2 (T2) SPD | 1P+N | In=20kA | Imax=40kA | Consumer unit incomer position | UKCA Certified (cert. 9113210923)

18 People watching this product now!
Description

Type 2 SPD 20kA 1P+N — Surge Protection Device for Consumer Units | UKCA Certified

The DSPD-20 is a Type 2 (T2) Surge Protection Device (SPD) in a compact 1-pole + neutral (1P+N) configuration, designed to protect electrical installations against transient overvoltages caused by lightning strikes, switching operations and other electromagnetic disturbances. Installed at the consumer unit main incomer position, this SPD clamps surge voltages before they can damage sensitive electronic equipment, appliances and building wiring.

BS 7671 (18th Edition) Amendment 2 (2022) introduced Regulation 443.4, which effectively requires surge protection on virtually all new domestic installations and consumer unit upgrades where the cost of the SPD is not disproportionate to the value of the equipment being protected. The DSPD-20 meets this requirement with a compact, cost-effective solution that occupies just 2 DIN rail modules in the consumer unit.

UKCA Certified under Safenet certificate 9113210923, this SPD delivers a nominal discharge current (In) of 20kA and maximum discharge current (Imax) of 40kA, with a voltage protection level (Up) of 1.4kV or less. It includes a visual status indicator to confirm operational status and an integrated backup fuse, making it a complete plug-and-protect solution for UK electricians.

Key Features

  • Type 2 (T2) surge protection — clamps transient overvoltages at the consumer unit incomer
  • 1P+N configuration — single-phase protection in a compact 2-module DIN rail format
  • In = 20kA nominal discharge current — handles typical lightning-induced surges
  • Imax = 40kA maximum discharge current — withstands severe surge events
  • Up ≤ 1.4kV voltage protection level — limits let-through voltage to safe levels
  • UKCA Certified (Safenet cert. 9113210923) — verified for the UK market
  • Visual status indicator — green (operational) / red (end of life, replace)
  • Meets BS 7671 Amendment 2 Regulation 443 requirements for surge protection
  • 35mm DIN rail mounting — fits all consumer units and standard distribution boards
  • Protects sensitive electronics — EV chargers, smart home devices, IT equipment, audio-visual systems
  • Essential for EV charging installations — protects the charger and vehicle onboard electronics

Technical Specification

Standard BS EN 61643-11 / IEC 61643-11
Product model DSPD-20-1PN
SPD type / class Type 2 (T2) / Class II
Configuration 1P+N (single-phase)
Nominal discharge current (In) 20kA (8/20µs)
Maximum discharge current (Imax) 40kA (8/20µs)
Voltage protection level (Up) ≤ 1.4kV
Maximum continuous operating voltage (Uc) 275V AC
Rated voltage 230V / 240V AC
Rated frequency 50/60 Hz
Response time ≤ 25ns
Protection modes L-N, L-PE, N-PE
Status indicator Visual window — green (OK) / red (replace)
Backup protection Integrated thermal disconnect
Module width 36mm (2 modules)
Protection grade IP20
Max wiring capacity 25mm²
Installation method 35mm DIN rail
Operating temperature -40°C to +70°C
UKCA certificate Safenet cert. 9113210923

Applications

  • Domestic consumer units — main incomer surge protection for homes and flats
  • EV charging installations — protects EV charger electronics and vehicle onboard systems
  • Smart home installations — protects connected devices, hubs and automation controllers
  • Home office and IT setups — protects computers, networking equipment and peripherals
  • Consumer unit upgrades — retrofit surge protection to comply with Amendment 2

Compliance & Certification

  • Manufactured to BS EN 61643-11 / IEC 61643-11
  • UKCA Certified — Safenet certificate number 9113210923
  • Meets BS 7671 (18th Edition) Amendment 2 Regulation 443 surge protection requirements
  • Suitable for use in installations compliant with BS 7671 (18th Edition IET Wiring Regulations)

Installation Notes

This SPD must be installed by a qualified electrician in accordance with BS 7671 (18th Edition). Always isolate the supply before installation. Install the SPD at the consumer unit main incomer position, connected between line, neutral and earth. The SPD should be protected by an upstream MCB or fuse rated as specified in BS EN 61643-11 (typically 32A–40A). Keep SPD connection cables as short as possible (maximum 500mm total lead length recommended) to minimise voltage let-through. Check the visual status indicator periodically — a red indicator means the SPD has reached end of life and must be replaced. The SPD is a sacrificial device designed to degrade after absorbing surge energy and must be replaced when the indicator shows red.

Additional information
Poles
Reviews (0)
0 reviews
0
0
0
0
0

There are no reviews yet.

Be the first to review “Type 2 SPD 20kA 1P+N – Surge Protection Device for Consumer Units | UKCA Certified”

Your email address will not be published. Required fields are marked *

1 2 3 4 5
1 2 3 4 5
1 2 3 4 5

Key Features
  • Switch disconnector designed to safely isolate the main circuit
  • DIN rail mounted — fits standard 35mm DIN rail for easy panel installation
  • Lockable in the Off position for lockout/tagout safety compliance
  • Contact status indicator window for clear visual on/off indication
  • Upper and lower incoming — flexible cable entry from either direction
  • Matches DGB1 series MCBs and RCBOs for consumer unit builds
  • Suitable for residential, commercial and industrial installations
  • Available in 1P, 2P, 3P and 4P configurations, 32A to 125A
  • Rated to IEC 60947-3 — certified to KEMA, CE, SEMKO and CB standards
  • IP20 protection grade with 10,000 electrical / 20,000 mechanical operation life
Specifications
Brand Terelec
SKU / Model DGG1-125-1P-100A
Current Rating 100A
Frame Current 125A
Voltage Rating AC 230V (1P) / AC 400V (3P, 4P)
Number of Poles 1 Pole
IP Rating IP20
Mounting 35mm DIN Rail
Terminal Capacity 35mm² (at 100A)
Terminal Type Fixed with screw
Incoming Method Upper and Lower
Lockable Yes
Indicator Window Contact status indication
Electrical Life 10,000 operations
Mechanical Life 20,000 operations
Rated Insulation Voltage 690V
Rated Frequency 50/60 Hz
Pollution Class Class III
Storage Temperature -25°C to +70°C
Installation Altitude ≤2000m
Standards IEC 60947-3
Certifications KEMA, CE, SEMKO, CB
Downloads

Download the product datasheet and supporting documents below:

To request a datasheet for a specific product, please contact us.